CYD-4.6 Hydraulic Disc Spring Operating Mechanism(Extended Type)
1.The mechanism uses disc spring as energy storage medium and hydraulic oil as transmission medium, which makes it easy to obtain high pressure and make its structure small and compact.
2.Fast action, sensitive response, large output power, free of operation and maintenance, low operating noise, high reliability, good matching of output characteristics and circuit breaker load characteristics.
3.Integrated piping design
4.Six modules
5.Complex structure, manufacturing process, materials, processing precision requirements are particularly high
Product Description
CYD-4.6 hydraulic disc spring actuator is suitable for the product package of three-phase mechanical linkage operation of 252KV-800KV sulfur hexafluoride high-voltage circuit breakers.
CYD-4.6 hydraulic disc spring actuator is an integrated structure of energy storage cylinder, working cylinder and control valve, which adopts annular energy storage cylinder and advanced sealing technology, realizing high reliability of hydraulic system. The product is characterized by advanced technical principle, good mechanical performance and high reliability.
Product Technical Parameters
1. Output power of breaking under rated voltage: 8750J
2. Rated voltage closing output power: 3795J
3. Rated voltage of motor: DC220V/AC220V/DC110V
4. Rated power of motor: 1000W
5. Closing time: 20-50ms
6.Displacement of safety valve startup under closing locking pressure:118±1mm
7. Displacement of oil pump stopping under closing and blocking pressure: 116±1mm
Application Scenarios
Installation place: indoor, outdoor organization box.
Ambient air temperature: upper limit +60℃, lower limit -30℃. If it is lower than -30℃, it should be specified in the order.
Altitude: ≤3000m.
Wind pressure not exceeding 700Pa (equivalent to wind speed 34m/s).
Relative humidity: the average daily relative humidity is not greater than 95%, the average monthly relative humidity is not greater than 90% (indoor); Salt spray, high humidity and heat areas should be considered in the design of the agency box condensation and precipitation effects.